ag真人游戏官网


您的位置:主页 > 产品展示 > MTL安全栅5000系列 > > MTL5022安全栅DO开关量

ag真人游戏平台 MTL5022安全栅DO开关量

MTL5022 SOLENOID/ ALARM DRIVER loop-powered, IIB The MTL5022 enables a device located in the hazardous area to be controlled by a switch or voltage change in the safe area. The MTL5022 can drive any certified intrinsically safe low-p
产品特点 产品参数 安装方法 技术资料
订购热线:
021-51090808
MTL5022 SOLENOID/
ALARM DRIVER
loop-powered, IIB
 
The MTL5022 enables a device located in the hazardous area to
be controlled by a switch or voltage change in the safe area. The
MTL5022 can drive any certified intrinsically safe low-power load,
as well as non-energy-storing simple apparatus such as an LED. The
unit’s input/output isolation allows the control switch to be connected
into either side of the 24V dc supply circuit. 



 
SPECIFICATION
See also common specification
Number of channelsOne
Zone 0, IIB, T4–6 hazardous area if suitably certified
Equivalent circuit
 
 
LED indicator
Yellow: status
Input voltage
20 to 35V dc
Hazardous-area output
Minimum output voltage:  12.9V at 60mA
Maximum output voltage: 24V from 133
Current limit:60mA
Maximum current consumption (with 60mA output)
115mA at 24V, typical
135mA at 20 to 35V dc, maximum
Maximum power dissipation within unit
1.5W at 24V
2.1W at 35V
Safety description
25V, 135Ω85mA,1Um = 250V rms or dc
 
SPECIFICATION
See also common specification
Number of channelsOne
Zone 0, IIB, T4–6 hazardous area if suitably certified
Equivalent circuit
 
 
LED indicator
Yellow: status
Input voltage
20 to 35V dc
Hazardous-area output
Minimum output voltage:  12.9V at 60mA
Maximum output voltage: 24V from 133
Current limit:60mA
Maximum current consumption (with 60mA output)
115mA at 24V, typical
135mA at 20 to 35V dc, maximum
Maximum power dissipation within unit
1.5W at 24V
2.1W at 35V
Safety description
25V, 135Ω85mA,1Um = 250V rms or dc

 